Not compatible
SOL-ARK 12K-2P-LL + Rolls S6 GC2-HC
- Voltage doesn't match: the 6 V battery won't work with this 48 V inverter.
Checked automatically against spec sheets. Not yet confirmed in a real install. Last checked 2026-10-14. We don't track firmware versions.
Size the battery cable and fuse for this pair in the build tool, from your run length.
Published limits, side by side
| Spec | SOL-ARK 12K-2P-LL | Rolls S6 GC2-HC |
|---|---|---|
| Voltage | 48 V accepts 43–59 V | 6 V |
| Current | Max battery current 220 A | Max charge Not published Max output Not published |
| Communication | Sol-Ark closed loop | None listed |
| Cable connection | Stud size Not published | Terminal DT |
Values come from each maker's documents. "Not published" means the maker doesn't state it.
Confirm with the makers before you buy
- Each product's current limits. One or both aren't published, so ask both makers.
- Which firmware versions support this pairing. We don't track firmware.
- That your cable lugs fit the inverter's battery studs (Not published) and the battery's terminals (DT).
- How to install both safely, from each maker's manual and your local code.
This result checks two things: the battery's voltage suits the inverter, and the inverter maker lists this battery for closed-loop communication (the battery tells the inverter how to charge it). It doesn't check current limits, charge settings, firmware, cable sizes, or safe installation. Confirm those with both makers before you buy.